Installation, Earthing & Safety MCQ – 31 previous year questions with solutions
Every Installation, Earthing & Safety question asked in GPSC AE Electrical, Supervisor Instructor, RRB JE, GPSC DEE Electrical and more — arranged topic by topic, with the exam and paper shown on each question.
The Indian Standard, IS 732 provides the code of practice for __________.
View answer & solution
Correct answer: A. Electrical wiring installations
Quick explanation
IS 732 provides a code of practice for electrical wiring installations. It covers design, selection/erection and safety-related practices for building/low-voltage electrical installations under its applicable edition.
IS 732 → electrical wiring installations
IS 3043 → earthing
As per IS 732, a leakage current in an installation should not exceed __________ of the full load current.
View answer & solution
Correct answer: C. 1/5000th
Quick explanation
Under the IS 732 rule referenced by the paper, installation leakage current should not exceed 1/5000 of the full-load current. Limiting leakage is important for shock protection, insulation health and avoiding unwanted protective-device operation.
According to IS 3043, the resistance of an earth connection for a large power station should be as low as possible, ideally not exceeding __________.
View answer & solution
Correct answer: A. 0.5 Ω
Quick explanation
For a large power station, earth resistance should be extremely low so high fault currents can return safely and protective devices operate quickly. The exam's IS 3043-based target is ideally not exceeding about 0.5 Ω.
EPR ≈ Ifault × Rgrid
Lower Rgrid → lower EPR for the same ground-fault current
The Indian Standard code of practice for earthing is specified in __________.
View answer & solution
Correct answer: B. IS 3043
Quick explanation
IS 3043 is the Indian Standard code of practice for earthing. It covers principles and practices for system earthing and protective/equipment earthing, including electrode arrangements and safety considerations.
IS 3043 → Earthing
IS 732 → Electrical wiring installations
The Indian Electricity Rules, 1956 were replaced by which of the following regulations?
View answer & solution
Correct answer: A. Central Electricity Authority Regulations (CEAR), 2010
Quick explanation
A — CEA Regulations, 2010. The safety provisions of the Indian Electricity Rules, 1956 were replaced by the CEA (Measures relating to Safety and Electric Supply) Regulations, 2010.
What is a key area of focus introduced in the National Electrical Code (NEC) of India, 2023?
View answer & solution
Correct answer: C. Regulations for electrical vehicle charging infrastructure
Quick explanation
The 2023 edition of India's National Electrical Code includes stronger/current provisions for modern electrical installations, including electric-vehicle charging infrastructure. That emerging installation area is the key focus among the options.
As per IS 732, the colour code for the earth wire in a flexible cable is __________.
View answer & solution
Correct answer: C. Green
Quick explanation
The protective earth conductor is identified by green in the convention used by this paper/IS 732 question. The distinctive earth-conductor colour prevents accidental connection as a live or neutral conductor.
Earth/protective conductor → green (exam convention)
Which modification in an earthing system most directly reduces earth resistance by improving the contact area between the electrode and surrounding soil?
View answer & solution
Correct answer: B. Increasing the effective contact area by using multiple or larger earth electrodes
Quick explanation
Multiple or larger electrodes increase electrode–soil contact and current-spreading area, lowering earth resistance.
The primary purpose of equipment earthing as per IS 3043 is to __________.
View answer & solution
Correct answer: B. Provide a safe path for leakage/fault current to flow
Quick explanation
Equipment earthing provides a low-impedance path for leakage/fault current from exposed conductive parts to earth/protective conductor so protective devices can operate rapidly and dangerous touch voltage is reduced.
live conductor → fault to enclosure → PE/earth path → source neutral/earth → protective-device operation
Earthing of electrical equipment is necessary to prevent:
View answer & solution
Correct answer: C. Electric shock
Quick explanation
C — Electric shock. Protective earthing bonds exposed conductive parts to a fault-current path and works with automatic disconnection to reduce shock risk.
Touch voltage approximately: Vtouch = If × Zearth-path
Lower fault-path impedance → larger protective fault current → faster disconnection
Regarding "Earthing" requirements as per Indian standards, consider the following: 1. The earth neutral conductor shall be earthed at the source and at each point of supply. 2. The resistance of the earth connection should be as high as possible for safety. 3. Periodic testing of earth pits is a mandatory safety requirement. Which of the statements given above is/are correct?
View answer & solution
Correct answer: A. 1 and 3 only
Quick explanation
Protective earthing provides a low-impedance path for fault current and stabilizes exposed conductive parts/neutral references. Earth resistance should be low enough to meet protection requirements and is checked periodically because soil/moisture/corrosion can change electrode performance. Key relation: Touch voltage and disconnection time depend on earthing and protective-device coordination.
Exam focus: Low earth resistance is desirable—not high resistance. Common trap: Never state that high earth resistance improves safety.
What does the diversity factor indicate in a lighting installation?
View answer & solution
Correct answer: C. The expected proportion of the total load used simultaneously
Quick explanation
C — The expected simultaneous use of the total load. Not all connected loads operate together; diversity factor = sum of individual maximum demands / maximum demand of the whole system (≥ 1).
Which type of wire is typically used to connect a ceiling fan to the power supply in residential buildings?
View answer & solution
Correct answer: A. Flexible copper wire
Quick explanation
A — Flexible copper wire. An appropriately rated, insulated flexible copper conductor is the suitable choice among the given options for the fan’s final supply connection.
R = ρl/A; voltage drop along a conductor = IR. Wire type alone does not specify its current rating.
D — Green. This is the traditional earthing-wire colour intended by the supplied options; modern protective-conductor identification commonly uses green-and-yellow.
KEY RULE / STANDARD NOTE: Traditional exam convention → earth = green. Modern protective conductor identification → green/yellow combination under contemporary standards.
Which of the following options correctly represents the connection principle used in staircase wiring?
View answer & solution
Correct answer: C. Two-way switches are connected in a crossover arrangement, with the lamp connected between phase and the common terminal
Quick explanation
C — Two two-way switches in a crossover arrangement. Their strappers interconnect, so either switch can complete or break the lamp circuit, letting one lamp be controlled from two places.
Which of the following is used as wiring material in residential building electrification?
View answer & solution
Correct answer: C. Copper
Quick explanation
C — Copper. It is the standard practical conductor for residential wiring because of its high conductivity, ductility and reasonable cost (silver is costlier).
Consider the following regarding Earth Leakage Protection: 1. An ELCB (Earth Leakage Circuit Breaker) detects small leakage currents to the earth. 2. Voltage-operated ELCBs are preferred over current-operated RCCBs in modern installations. 3. A 30mA RCCB is generally used for personal protection against electric shock. Which of the statements given above is/are correct?
View answer & solution
Correct answer: B. 1 and 3 only
Quick explanation
An RCCB/RCD detects imbalance between live and neutral currents caused by leakage to earth and is used for shock protection. An MCB protects conductors against overload and short circuit. Key relation: Typical additional personal protection uses 30 mA RCD/RCCB.
Exam focus: RCCB → leakage; MCB → overcurrent; SPD → transient surge. Common trap: Do not expect an RCCB alone to provide overload protection.
Regarding electrical safety and protection devices: 1. An RCCB (Residual Current Circuit Breaker) protects against earth leakage currents,which helps prevent electric shocks. 2. An MCB (Miniature Circuit Breaker) provides protection against both overload and short-circuit faults. 3. Surge Protection Devices (SPDs) are designed to handle sustained overvoltage conditions. Which of the statements given above is/are correct?
View answer & solution
Correct answer: A. 1 and 2 only
Quick explanation
An RCCB/RCD detects imbalance between live and neutral currents caused by leakage to earth and is used for shock protection. An MCB protects conductors against overload and short circuit. Key relation: Typical additional personal protection uses 30 mA RCD/RCCB.
Exam focus: RCCB → leakage; MCB → overcurrent; SPD → transient surge. Common trap: Do not expect an RCCB alone to provide overload protection.
What is the primary function of an RCCB (Residual Current Circuit Breaker) in an electrical system?
View answer & solution
Correct answer: D. To protect humans from electric shock due to earth faults
Quick explanation
An RCCB protects people against dangerous earth-leakage/residual current by comparing the currents in live and neutral conductors. If the imbalance exceeds its trip threshold, it disconnects the circuit rapidly.
Regarding the selection of industrial cables, consider the following: 1. XLPE insulated cables have a higher continuous operating temperature than PVC cables. 2. The short-circuit rating of a cable is independent of the insulation material. 3. Voltage drop calculation is mandatory for selecting long cable runs. Which of the statements given above is/are correct?
View answer & solution
Correct answer: C. 1 and 3 only
Quick explanation
Industrial cable selection must satisfy current-carrying capacity, voltage drop, installation conditions and short-circuit withstand. XLPE insulation generally permits a higher continuous conductor temperature than PVC. Key relation: Voltage drop≈I(R cosφ+X sinφ)L; adiabatic short-circuit relation I²t≈k²S².
Exam focus: Check ampacity, voltage drop and short-circuit withstand together. Common trap: Cable short-circuit rating is not independent of insulation temperature limits.
Voltage drop≈I(R cosφ+X sinφ)L; adiabatic short-circuit relation I²t≈k²S².
The 'cone of protection' method, specified in lightning protection standards, is used to determine the area protected by a
View answer & solution
Correct answer: B. Lightning rod (air terminal)
Quick explanation
The cone-of-protection method estimates the zone shielded by a lightning air terminal/lightning rod. A geometric protective zone is drawn below/around the rod so equipment or building portions inside the zone are considered protected under that simplified method.
Air terminal → interception
Down conductor → current path
Earth termination → dissipation
Consider the following statements regarding Preventive Maintenance of industrial electrical systems: 1. Thermography is used to detect "hot spots" in electrical connections and panels. 2. Measurement of Earth Resistance should be done periodically using an Earth Tester. 3. Dielectric strength testing is performed only on cables and never on transformer oil. Which of the statements given above is/are correct?
View answer & solution
Correct answer: A. 1 and 2 only
Quick explanation
Preventive maintenance aims to detect deterioration before failure. Electrical programs combine thermal inspection, insulation testing, earth-continuity/resistance checks, contact tightening, protection testing and oil diagnostics where applicable. Key relation: Thermal principle: abnormal I²R heating reveals high-resistance connections. Dielectric-strength tests determine the electric stress at which insulation breaks down under the specified test method.
Exam focus: Thermography = hot spots; earth tester = grounding health; BDV test = transformer oil insulation quality. Common trap: Believing dielectric testing applies only to solid cable insulation.
Thermal principle: abnormal I²R heating reveals high-resistance connections. Dielectric-strength tests determine the electric stress at which insulation breaks down under the specified test method.
How many Installation, Earthing & Safety MCQs are on SarkariResultOut?
31 previous year Installation, Earthing & Safety questions across 8 topics, each with the exam it was asked in, the verified answer and a step-by-step solution.
Which exams asked these Installation, Earthing & Safety questions?
GPSC AE Electrical · AE R&B · 2025 · Series M; Supervisor Instructor · Part B Technical · 2026; GPSC DEE Electrical · DEE Master paper · 2026; Vidyut Sahayak JE · Second tier · 2024; RRB JE · CBT 2 Electrical · Shift 1 and more.
Can I download Installation, Earthing & Safety MCQs as a PDF?