Q1Hard
A fault occuring at the terminals of an unloaded synchronous generator operating at its rated voltage has resulted in the following values of currents and voltages:Ia0 = j2.37 p.u.Ia1 = – j3.05 p.u.Ia2 = j0.68 p.u.Va0 = Va1 = Va2 = 0.237 p.u.
Which one of the following faults has occurred?
View answer & solution
Correct answer: B. L - L - G fault
Quick explanation

For a double-line-to-ground fault on phases b and c, the unfaulted phase current Ia is zero and the fault-point sequence voltages satisfy the appropriate equal-voltage relation. Three independent signatures agree: zero sequence present → ground fault; Ia=0 → phase a healthy; negative sequence present → unbalanced two-phase involvement.

Exam focus: Fault ID shortcut: zero-sequence present means the ground path participates. Common trap: Selecting a 3-phase fault despite nonzero I0 and I2.

Ia=I0+I1+I2. Here Ia=0. Phase transformation: [Va Vb Vc]^T = A[V0 V1 V2]^T.
Verified · SRO editorial deskSolution page → Report
Q2Hard
If all the sequence voltages at the fault point in a power system are equal, then fault is __________
View answer & solution
Correct answer: A. LLG fault
Quick explanation

In a line-to-line-to-ground (LLG) fault, positive-, negative- and zero-sequence networks are all involved and their sequence voltages at the fault point are equal because the three sequence networks meet at a common fault-point voltage.

V₀ = V₁ = V₂
Verified · SRO editorial deskSolution page → Report

Line-to-Line Fault (1)

Q3Moderate
Consider following statements: Assertion: When a line-to-line (L-L) fault takes place at the terminals of an open-circuited generator, the phase voltages are sometimes indeterminate though line voltages are always determinable. Reason: During L-L fault, a zero-sequence voltage is always indeterminate. Of these statements:
View answer & solution
Correct answer: A. Both Assertion and Reason are true and Reason is the correct explanation of Assertion.
Quick explanation

For an L-L fault there is no zero-sequence current, so the zero-sequence network is not fixed by current flow. At open-circuited generator terminals this can leave the common zero-sequence voltage reference indeterminate even though line-to-line voltages remain uniquely determined. Hence both assertion and reason are true and the reason explains the assertion: option A.

L-L fault: I0=0; line voltages are independent of common zero-sequence voltage shift
Verified · SRO editorial deskSolution page → Report

Synchronous Generator Reactances (1)

Q4Hard
Which of the following reactances is eliminated first in synchronous generator just after the symmetrical fault?
View answer & solution
Correct answer: B. Damper winding reactance
Quick explanation

Immediately after a sudden symmetrical fault, damper-winding currents produce the strongest opposing transient flux and therefore the smallest subtransient reactance. The effect associated with the damper winding decays first as those induced currents die out rapidly.

Verified · SRO editorial deskSolution page → Report

Unsymmetrical Faults (1)

Q5Easy
Which one of the following is series unsymmetrical fault in power system?
View answer & solution
Correct answer: B. Open conductor fault
Quick explanation

B — Open conductor fault. Breaking one or two phase conductors interrupts the series current path and creates an unbalanced three-phase condition.

KEY CLASSIFICATION: Series fault → open conductor(s). Shunt faults → L-G, L-L, L-L-G, 3-phase faults.