A three−phase transformer having a line voltage ratio of 400/33000 V is connected in the star-delta. The CTs on the 400V side have a CT ratio of 1000/5. What must be the ratio of CTs on the 33000 side?
⚑ Report issue
Found a wrong answer, translation, image or source problem? Send it to editorial review.
Transformer differential protection requires the CT secondary currents presented to the relay to compensate for the transformer ratio and phase-connection effects. Using the given 400/33 kV transformer and 1000/5 CT on the LV side, the matching HV-side CT ratio corresponds to the keyed 7/5 value.
Formula / Key Relation
Transformer line-current ratio:
ILV / IHV = VHV / VLV = 33000/400 = 82.5
Then include √3 CT-connection compensation for differential balance.
Detailed Explanation
Concept & ReasoningIn transformer differential schemes, CT connections are normally opposite to the power-transformer winding connections to compensate the 30° phase shift. The current magnitude on each side is inversely proportional to line voltage for the same MVA, and the delta-connected CT group introduces a √3 factor. A rigorous calculation should write line currents and relay-side currents explicitly before choosing the CT ratio.How to Solve It in the ExamProtection CT matching = transformer current ratio + CT star/delta compensation.Important Exam PointDraw transformer winding and CT connections before calculating relay currents.Related Revision PathThis question sits in the revision path Power System…
Concept & Reasoning
In transformer differential schemes, CT connections are normally opposite to the power-transformer winding connections to compensate the 30° phase shift. The current magnitude on each side is inversely proportional to line voltage for the same MVA, and the delta-connected CT group introduces a √3 factor. A rigorous calculation should write line currents and relay-side currents explicitly before choosing the CT ratio.
How to Solve It in the Exam
Protection CT matching = transformer current ratio + CT star/delta compensation.
Important Exam Point
Draw transformer winding and CT connections before calculating relay currents.
Related Revision Path
This question sits in the revision path Power System → Protection → Differential Protection .
Quick Trick
Protection CT matching = transformer current ratio + CT star/delta compensation.
Common Mistake
Using only 82.5:1 transformer line-current ratio and ignoring CT connection compensation.
Exam Tip
Draw transformer winding and CT connections before calculating relay currents.
SEO + Knowledge GraphRelated PYQs & Exam ContextExam path, knowledge path and deeper practice links.
Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198Assistant Engineer (Electrical), Class-2, Road and Building Department2025Q. 198